Item |
Unit |
Value |
CY |
YT , CYT |
Rated voltage |
kV |
550 |
Rated frequency |
Hz |
50 |
Rated current |
A |
3150 |
4000 |
Rated short-circuit breaking current |
kA |
50 |
63 |
Short-line fault breaking current |
kA |
45 |
56.7 |
Rated out-of-phase breaking current |
kA |
12.5 |
15.75 |
Rated peak withstand current |
kA |
125 |
160 |
Rated short-circuit making current (peak) |
kA |
125 |
160 |
Rated short-time withstand current |
kA |
50 |
63 |
Rated short-circuit duration |
s |
3 |
Rated line charging breaking current (rms) |
A |
500 |
5 min power-frequency withstand voltage at zero gauge pressure of SF6 gas (rms) |
Incoming and outgoing line of one pole |
kV |
476 |
Pole to earth |
kV |
476 |
1min power-frequency withstand voltage (rms) |
Incoming and outgoing line of one pole |
kV |
740 (+315) |
Pole to earth |
kV |
740 |
Lightning impulse withstand voltage, full wave 1.2/50μs (peak) |
Incoming and outgoing line of one pole |
kV |
1675+ (450) |
Pole to earth |
kV |
1675 |
Operating wave impulse 1.2/2500μs (peak) |
Incoming and outgoing line of one pole |
kV |
1175+ (450) |
Across the breaker |
kV |
1800 |
Pole to earth |
kV |
1300 |
Shunt capacitance |
pF |
2500 |
Shunt closing resistance |
Ω |
400±5% |
Rated SF6 gas pressure (at 20℃) |
MPa |
0.6 |
Moisture content of SF6 gas in circuit breaker itself (when leaving the factory) |
ppm |
≤150 |
Annual leakage rate of SF6 gas |
% |
≤1 |
Weight of SF6 gas in single pole |
kg |
20 (without resistor)/25 (with resistor) |
Weight of single-pole circuit breaker |
kg |
2840 (without resistor)/3800 (with resistor) |
Closing/opening operating force |
kN |
60/130 |
Allowable tensile force of terminal |
Horizontal longitudinal |
N |
2800 |
Horizontal transverse |
N |
2400 |
Vertical |
N |
1000 |
|
|
|
|
|
|
|