GIS, circuit breaker, disconnector & its parts |
|
|
CT30-126 Spring operating mechanism |
|
Our CT30-126 is appropriate to the 126kV HV SF6 circuit breaker, the performance meets the requirement of IEC56 Alternating current high-voltage circuit-breakers. It contains two modes of electromotor and hand machine.
Parameters
NO. |
ITEM |
UNIT |
SPECIFICATIONS |
NOTES |
1 |
Switching power |
J |
2600-3100 |
|
2 |
Motor (AC/DC) |
Power |
W |
600 |
3 |
Voltage |
V |
220/110 |
4 |
Opening/closing coil |
Rated voltage |
V |
DC220/DC110 |
5 |
Current |
A |
2≤3.7 |
6 |
Output shaft rotation |
degree |
45 |
7 |
Control voltage of the secondary circuit |
V |
DC220/DC110 |
8 |
Rod travel |
MM |
1000-3 |
9 |
Heater |
Voltage |
V |
AC220 |
Power |
W |
150 |
CT30-SP mechanism is used to match the 126kV SF6 post circuit breaker.
|
|