Our CJZ4 absorbed the advantages of like products , and optimized some structures, now the product has excellent structure, rational organization, reliable and easy operation.
CJZ4 is apply to operate the 126 kV GIS, operating the inspectionsitting ES, and it has two modes of electromotor and hand machine. Switching on /off can be operated both remote and local. The performance can meet the industrial requirements IEC56 Alternating current high-voltage circuit-breakers.
Parameters
NO. |
ITEM |
UNIT |
SPECIFICATIONS |
NOTES |
1 |
Output shaft rotation |
Degree |
90 |
|
2 |
Rated voltage |
Motor |
V |
DC220/AC220 |
AC/DC |
Control loop |
DC220/DC110 |
|
Heater |
AC220 |
|
3 |
Motor rated power |
W |
240 |
|
4 |
Motor rated current |
A |
2 |
|
5 |
Heater power |
W |
80 |
|
6 |
Electric opening time |
S |
≤4 |
|
7 |
Electric closing time |
S |
≤4 |
|
8 |
Service life |
Time |
3000 |
Reliability above 10000 times |
9 |
Weight |
Kg |
40 |
|
The opening/closing time is calculated from the given operating signal to regulated opening/closing position.
|